11/10/97
Has anyone had experience with eliminating excessive amounts of dust in
their EM rooms?
I moved into a newly renovated suite of rooms over a year ago. Since that
time we have been plagued by dust and dirt. It has become almost impossible
to maintain uncontaminated grids or negatives and prints without dust or
scratches. For example you cannot leave a negative on a light box overnight
because it is covered by a thin film of dust by the next day.
The Engineering department had the ductwork cleaned and higher efficiency
filters installed on the fan units supplying air to the suite during
renovations. They claim the supply air is the same quality as that in my
previous location in another building (where excessive dust was not a
problem).
An outside consultant has monitored the rooms and found particle counts
between 20,000 and 50,000 in the 0.5 micron size range, per cubic foot.
They recommend installing HEPA filters on all supply air ducts to reach
class 1,000 conditions.
The Engineering department is reluctant to install 10 or more HEPA filter
units due to the cost and the necessary ductwork reworking. They claim the
supply air is clean and the filters will not solve the problem. They would
like to install electrostatic particle precipitators in each room to scrub
the air clean.
Does anybody have any experience with electrostatic precipitators and which
type is best?
Is there a standard for airborne particles within a microscopy facility?
Is the class 1,000 condition recommended by the consultant excessive?
We are about to begin renovations for our light microscope area which will
have a number of digital imaging stations in addition to film and video.
What recommendations can I make to engineering in the design of the HVAC
system to address this issue during construction?
Sorry for the excessive bandwidth of this message but I wanted to be as
explicit as possible.
Frank Macaluso tel: 718-430-3547
Analytical Imaging Facility fax: 718-430-8996
Albert Einstein College of Medicine e-mail: macaluso@aecom.yu.edu
1300 Morris Park Avenue
Bronx, NY 10461
thought occured to me. You might ask your Engineers if the return air
passes through a "plenum" above the ceiling or below the floor. This is
just a fancy word for saying that the open space (above or below) acts
as the return duct. If this is the case, and it often is, that might be
the source of a large part of your problem. You've probably seen, or
can imagine, the cleanliness of these areas! If so, regardless of
filtration systems, you should probably start with a dedicated HVAC
system for the microscopy rooms and incorporating duct work for both
supply and return sides. Then add filtration as necessary to achieve
acceptable cleanliness. It may be that, in your circumstances, Class
1000 is more than really necessary but you're probably in for some
expensive retrofitting in any event.
Stephen A. Shaffer
MicroDataware
sshaffer@microdataware.com (business)
concentrations of ozone and contribute to rapid deterioration of rubber
parts of equipment. Best test is the lifetime of a stretched rubber
band; compare to control prep'n perhaps at home.
Air-conditioner type filters treated with a polyethylene glycol spray
may stop the dirt to a great extent without going to the expense of HEPA
filters. Under the conditions you describe, the initial cost might not
be as big a burden as the cost of frequent replacements!
Jerry Freed
jjfreed@netreach.net
50K particles in the 0.5 micron range per cubic foot. From experience, I
would be surprised if you get a visible film of dust observed on a light
background overnight, but perhaps a visible film of dust on a dark shiny
negative as you describe sounds reasonable, especially when viewed by
scattered light. You definitely shouldn't get anything you can feel with
your fingers overnight.
I recommend the article "Particulate Fallout Predictions for Clean Rooms"
by Otto Hamburg in The Jour. of Environmental Sciences, May/June 1982
pp.15-20.
You can set out "witness plates" for various lengths of time and observe
the amount of fallout you get and compare these results with environments
of different load suspensions. Your witness plates should be identical to
the substrates of interest....TEM grids and negatives, and be in the same
place in your room. This can make a big difference. Particulate
characteristics, air flow, humidity, substrates, etc. will be different
from one person's environment to another's, meaning you cannot readily
expect one person's experiences to be applicable to yours.
We have a particle prep lab that ranges between 1K-50K particles >= 0.5
micron per cubic foot, depending where you are and what phase the moon is
in. We then have < Class 10 areas embedded within that where samples may
be exposed to air. (Assuming that my laser counter's calibration is still
good). Within the 20-50K areas that would be somewhat similar to yours, I
would not expect to find significant dust accumulation on negatives
overnight. However, I would guess that if the air was very dry, and there
was plenty of air flow across the negatives, perhaps they would
electrostatically collect enough by the next day to be a problem. I would
not leave TEM grids out in this air if I was concerned about contamination.
Typical unfiltered office and home air where there is no smoke has about a
few billion particles >= 0.5 microns per cubic foot. So if you have a
rough idea of how rapidly dust accumulates there, you can apply the rules
of 10 to get a VERY ROUGH idea of what you would get in the same
environment if it had a few orders of magnitude less particulate. Again, I
repeat, very rough.
I also have a story. I once worked in a cleanroom that had about 10,000
particles >= 0.5 micron per cubic foot in most areas (Class 10,000), and
some Class 10 areas. About once every several days, I would find an
enormous amount of dust on everything in the Class 10,000 areas and the
clean room would have to be thoroughly cleaned. It appeared to be caused
by "burps" in the plenum structure, caused by momentary pressure
differentials, that allowed dust that had accumulated there to burp through
seams in the ceiling. Solution: seal the seams. So your average dust
suspension measurements may not reflect momentary, but significant, surges,
for whatever reason.
Other useful references are:
FED-STD-209E Federal Standard for Clean Room and Work Station Requirements
for Controlled Environments
MIL-STD 1246 Military Standard for Product Cleanliness Levels
Hope this helps.
Cynthia J. Zeissler
Physical Scientist
National Institute of Standards and Technology
cynthia.zeissler@nist.gov
301-975-3910
They are very efficient at removing particles, but the air has to flow
through the plates, so in your case they would have to be installed in the
AC inputs. (It's different conditions when the particles are continuously
introduced than when they are stirred up off the floor.) Furthermore, the
ozone production already mentioned is a problem; activated charcoal filters
after the precipitators could solve it. If you go this route, there will
have to be regular maintenance of both the precipitators & the filters.
Good luck.
Yours,
Bill Tivol
tivol@wadsworth.org